What is Circulation (outdoor)?

The circulation pumps are the heart of the water loop: they move the entire pool volume through filter and heat exchanger several times a day (DIN 19643 turnover).

As a 24/7 base load they are one of the biggest power consumers in the facility. With variable-speed pumps (VFD) the AI matches flow to bather load instead of running flat-out — saving a large share of the pumping electricity.

Schematic (native, live)

Solar gain, night radiation, wind, pool cover as the lever:

Sun/windOutdoor poolPool cover

Overview: The Glass Pool → · Markets: pool markets →

Live —

loading

What the AI does

The AI controls pump speed to bather load (VFD) instead of full load and shifts circulation peaks into PV hours.

Method proven on a live European reference aquatic center; presented anonymously.

Value calculator

Estimate from metered / design values. Zero-grid-import windows are real (metered).

Standards & norms

What the rules require — Circulation (outdoor)

Grounded in DIN 19643, VDI 2089, DGfdB and the German Buildings Energy Act. Same knowledge base as the European reference site; presented anonymously.

What does DIN 19643-1 require regarding Filtration and circulation?

DIN 19643-1 prescribes a maximum residence time of the pool water, depending on pool type: swimmer pools 4 h turnover, non-swimmer/paddling 1-2 h. This sets the minimum filter flow rate. For a 242 m³ lap pool at 4 h turnover that is 60.5 m³/h of filter capacity. Filter backwash once per day or above 0.5 bar differential pressure. Backwash water is warm (pool temperature − 3-5 K) and therefore a valuable heat-pump source.

Basis: DIN 19643-1

What does VDI 2089 Sheet 2 require regarding Pool evaporation balance?

Evaporation from the water surface is the dominant heat loss in an indoor pool (60-80 %). Smith/Löf variant of the Carrier formula: m_evap [kg/h] = β × A [m²] × (p_w_pool − p_w_hall) [kPa]. β-coefficient per VDI 2089 Sheet 2 Tab. 4: 0.013 unused pool (covered), 0.040 normal use, 0.080 wave/diving pool. Evaporation enthalpy at 30 °C: 0.694 kWh/kg. Pool saturation vapour pressure via the Magnus formula: 611.2 × exp(17.62 × t / (243.12 + t)) Pa.

Basis: VDI 2089 Sheet 2

What does VDI 2089 Sheet 2 require regarding Outdoor-pool convection and radiation?

Outdoor pools have higher convection and radiation losses. Convection: h_conv = 4 + 11 × v_wind [W/(m²·K)] with v in m/s. At 1 m/s wind: h ≈ 15 W/(m²·K). Night radiation (clear sky): ~60 W/m² over a 10 h night. Solar gain during the day (global radiation × absorptivity 0.82 × 12 h) is a credit — in high summer it can drop the heat demand close to zero. A night cover reduces both evaporation (−85 %) and radiation loss (−90 %).

Basis: VDI 2089 Sheet 2

What does DGfdB R 60.03 require regarding Outdoor-pool heat-up?

DGfdB guideline R 60.03 on heating public outdoor pools: heat-up phase in April over 30 days, raising the set-point from 10 to 22 °C; slow heat-up (45 days) or solar absorbers as a pre-heat stage save energy. For 2,508 m³ of water × 12 K × 1.16 kWh/(m³·K) = 34,928 kWh — spread over 30 days that is 1,164 kWh/d of extra load. Recommendation: heat up via a pool heat pump on a warm source (backwash water already at 15 °C before season start) instead of a gas peak boiler. A pool cover shortens the time (solar gain by day, loss reduction by night).

Basis: DGfdB R 60.03

What does DGfdB R 65.10 require regarding Energy management of public pools?

DGfdB guideline R 65.10 fixes the order for refurbishments: 1) reduce losses (envelope, pool cover, insulate the surge tank, ventilation heat recovery), 2) recover heat (heat recovery, waste-water heat, filter backwash as a heat-pump source), 3) generate efficiently (heat pump > CHP > gas). This hierarchy is decisive for public grant applications: funders check whether losses were reduced before the generation investment. Concretely: insulate the surge tank, add an outdoor-pool night cover and service the ventilation heat recovery before or together with the heat-pump installation.

Basis: DGfdB R 65.10