Outdoor-pool loop — seasonal; cover and solar gain are the lever. Part of the glass family — like our glass BESS, biogas plant and CHP.
The outdoor pool runs only in season (~week 20 to September). By day it gains heat from the sun (absorption ~0.82); at night it loses heat by radiation to the clear sky, and by day through wind (convection).
The biggest lever is the pool cover: it stops night radiation and evaporation. The AI weighs solar gain, wind and cover against each other and heats preferentially with PV surplus.
Solar gain, night radiation, wind, pool cover as the lever:
Overview: The Glass Pool → · Markets: pool markets →
Method proven on a live European reference aquatic center; presented anonymously.
Estimate from metered / design values. Zero-grid-import windows are real (metered).
Grounded in DIN 19643, VDI 2089, DGfdB and the German Buildings Energy Act. Same knowledge base as the European reference site; presented anonymously.
DGfdB guideline R 60.03 on heating public outdoor pools: heat-up phase in April over 30 days, raising the set-point from 10 to 22 °C; slow heat-up (45 days) or solar absorbers as a pre-heat stage save energy. For 2,508 m³ of water × 12 K × 1.16 kWh/(m³·K) = 34,928 kWh — spread over 30 days that is 1,164 kWh/d of extra load. Recommendation: heat up via a pool heat pump on a warm source (backwash water already at 15 °C before season start) instead of a gas peak boiler. A pool cover shortens the time (solar gain by day, loss reduction by night).
Basis: DGfdB R 60.03
Evaporation from the water surface is the dominant heat loss in an indoor pool (60-80 %). Smith/Löf variant of the Carrier formula: m_evap [kg/h] = β × A [m²] × (p_w_pool − p_w_hall) [kPa]. β-coefficient per VDI 2089 Sheet 2 Tab. 4: 0.013 unused pool (covered), 0.040 normal use, 0.080 wave/diving pool. Evaporation enthalpy at 30 °C: 0.694 kWh/kg. Pool saturation vapour pressure via the Magnus formula: 611.2 × exp(17.62 × t / (243.12 + t)) Pa.
Basis: VDI 2089 Sheet 2
Outdoor pools have higher convection and radiation losses. Convection: h_conv = 4 + 11 × v_wind [W/(m²·K)] with v in m/s. At 1 m/s wind: h ≈ 15 W/(m²·K). Night radiation (clear sky): ~60 W/m² over a 10 h night. Solar gain during the day (global radiation × absorptivity 0.82 × 12 h) is a credit — in high summer it can drop the heat demand close to zero. A night cover reduces both evaporation (−85 %) and radiation loss (−90 %).
Basis: VDI 2089 Sheet 2
DGfdB guideline R 65.10 fixes the order for refurbishments: 1) reduce losses (envelope, pool cover, insulate the surge tank, ventilation heat recovery), 2) recover heat (heat recovery, waste-water heat, filter backwash as a heat-pump source), 3) generate efficiently (heat pump > CHP > gas). This hierarchy is decisive for public grant applications: funders check whether losses were reduced before the generation investment. Concretely: insulate the surge tank, add an outdoor-pool night cover and service the ventilation heat recovery before or together with the heat-pump installation.
Basis: DGfdB R 65.10
Uninsulated surge tanks (steel or concrete, in the ground) lose heat continuously. Uninsulated U-value: 2.0 W/(m²·K) against ground (12 °C). Insulating with 80 mm PUR rigid foam reduces U to 0.32 W/(m²·K) — a factor of 6. Investment: 250-350 €/m² of tank wall including water-tightness and mould protection. For a 55 m² surge tank: 124 kWh/d uninsulated → 20 kWh/d insulated = 38 MWh/a saved, ~3,400 €/a in gas. Plus avoidance of condensation corrosion on the outside.
Basis: Practice (KSB, FLL)