The Glass Pool · RLT

Air handling (total)

Ventilation/dehumidification — the silent 24/7 load, with heat recovery. Part of the glass family — like our glass BESS, biogas plant and CHP.

Air handling (total)
Outdoor air Fresh air Heat recovery Heating coil Hall Exhaust
Glass-box in 4 steps

Understand → See it live → What the AI does → Your benefit

Step 1 of 4
1
Understand
2
See it live
3
What the AI does
Your benefit

What is Air handling (total)?

The full air-handling system unites outdoor, supply, exhaust and discharge air, heat recovery and the heating coil into one controlled unit — about 36,000 m³/h at the reference site. It holds the hall climate (30 °C / 55 % RH) and is, together with dehumidification, the biggest heat consumer of the facility.

Traditionally these parts run side by side on fixed setpoints. Treated as one system, the big levers appear only in their interplay: minimum air change, maximum recovery, reheating only as the remainder.

Schematic (native, live)

Dehumidification with heat recovery (DIN 1946-4, 36,000 m3/h):

Exhaust humidHeat recovery 65%Supply air dry

Overview: The Glass Pool → · Markets: pool markets →

Live —

loading

What the AI does

The AI runs the whole air-handling chain as one optimisation: minimum air change for the humidity, maximum recovery use, reheating only as the remainder — flexible shares into favourable windows.

Related causal chains (K01, K02)

Method proven on a live European reference aquatic center; presented anonymously.

Value calculator

Estimate from metered / design values. Zero-grid-import windows are real (metered).

Standards & norms

What the rules require — Air handling (total)

Grounded in DIN 19643, VDI 2089, DGfdB and the German Buildings Energy Act. Same knowledge base as the European reference site; presented anonymously.

What does VDI 2089 Sheet 1 require regarding Pool-hall ventilation?

VDI 2089 Sheet 1 defines the target hall climate: air temperature 30 °C ± 2 K, relative humidity 55 % ± 5 %. Outdoor-air rate at least 30 m³/h per person at full occupancy, at least 4 L/(s·m² of water surface) in base mode. For a hall with 355 m² water surface: 4 × 355 × 3.6 = 5,112 m³/h minimum; in practice VDI recommends ~16,000 m³/h for comfort and pollutant removal (trihalomethanes). Heat recovery via plate exchanger at 65-75 % efficiency is standard.

Basis: VDI 2089 Sheet 1

What does VDI 2089 Sheet 1 require regarding Dehumidification?

When hall humidity is too high (rH > 65 %) the traditional fix is raising the outdoor-air rate — which doubles the heat loss in winter. The modern approach is a dehumidifying heat pump (sorption wheel or reversible compressor) that removes water directly from the hall air without raising outdoor air. Investment 30-80 k€ depending on size, payback 4-7 years. On a hall running 16,000 m³/h in cold winters a sorption wheel can save 30-50 % of the ventilation heating energy.

Basis: VDI 2089 Sheet 1

What does VDI 2089 Sheet 2 require regarding Pool evaporation balance?

Evaporation from the water surface is the dominant heat loss in an indoor pool (60-80 %). Smith/Löf variant of the Carrier formula: m_evap [kg/h] = β × A [m²] × (p_w_pool − p_w_hall) [kPa]. β-coefficient per VDI 2089 Sheet 2 Tab. 4: 0.013 unused pool (covered), 0.040 normal use, 0.080 wave/diving pool. Evaporation enthalpy at 30 °C: 0.694 kWh/kg. Pool saturation vapour pressure via the Magnus formula: 611.2 × exp(17.62 × t / (243.12 + t)) Pa.

Basis: VDI 2089 Sheet 2

What does DGfdB R 65.10 require regarding Energy management of public pools?

DGfdB guideline R 65.10 fixes the order for refurbishments: 1) reduce losses (envelope, pool cover, insulate the surge tank, ventilation heat recovery), 2) recover heat (heat recovery, waste-water heat, filter backwash as a heat-pump source), 3) generate efficiently (heat pump > CHP > gas). This hierarchy is decisive for public grant applications: funders check whether losses were reduced before the generation investment. Concretely: insulate the surge tank, add an outdoor-pool night cover and service the ventilation heat recovery before or together with the heat-pump installation.

Basis: DGfdB R 65.10

What does DIN 1946-4 require regarding Ventilation hygiene (hospitals/pools)?

DIN 1946-4 governs ventilation with hygiene requirements. For pool halls: filter class F7 minimum, 6-month service interval. Plate heat-recovery exchangers must be able to drain condensate. Hygiene inspection every 2 years (logged in the maintenance record). Pool-specific: because of chloramines, corrosion-resistant materials (V4A stainless, plastic) are required in the exhaust stream; aluminium exchangers are not permitted in the pool-hall exhaust air.

Basis: DIN 1946-4

More pool worlds

Browse the 40 wizards

← PreviousDischarge air▦ All 40
License the software

Bring the glass-box AI to your pool.

Stromfee.US licenses the pool & wellness HVAC AI — proven in Europe, deployed on your existing plant. Single property, portfolio or chain.

Request software license →